Item | OM-8 |
---|---|
Torque (Nm) | 1500 |
Torque (in-lb) | 13280 |
Size of Output Drive (mm) | ●35 |
Depth of Output Drive (mm) | 60 |
Flange (ISO 5211) | F12 or F14 |
Run Time (sec / 90°) | 51 |
Manual Override | Hand-Wheel |
Weight (kg) | 36 |
Weight (lb) | 79.4 |
Thermal trip temperature:
AC motor: 125±5℃ (257±9℉)
DC motor: 90±5℃ (194±9℉)
A space heater can increase the internal temperature and keep dry inside actuator to avoid the freezing lubricant and moisture causing actuator failure under low temperature or high humidity. Heater is not recommended if the ambient temperature is above 35℃/95℉. However, when the temperature varies much from day to night or between summer and winter, heater and thermostat (25±5℃/77±9℉) are recommended.
The option can switch the heater off when the temperature inside the actuator is over 25℃/77℉.
The standard model equips with the 1st & 2nd switches for fully-open and fully-closed. The option consists of the 3rd & 4th auxiliary switches which provide dry contacts for fully-open and fully-closed.
The option can provide 4-20mA output signal for position indicator and etc.
Actuator can be operated according to input signal and provide the output signal for indicator.
Input signal : 4-20mA, 1-5V, 2-10V.
Output signal : 4-20mA, 2-10V.
The option is suggested for higher starting frequency.
The option can be ordered with On/Off actuators.
The selection has 1k or 5k ohm resistance values.
It provides feedback signal for position indicator.
The option can be used in filed control. It provides Local/Remote selection switches and Open/Close selection switches. It is available for OM-2 to OM-13,OM-F,OM-G actuators and must be ordered with actuator.
The option can provide over-load protection. It is available for OM-2 to OM-13,OM-F,OM-G actuators, and must be ordered with actuator.
The option can adjust the actuator speed (running time) from standard to 30s, 60s and so on (Max. 200s) according to user’s need. It is available for OM-2 to OM-13, AC 220V,1-PH and OM-2 to OM-8, 110VAC actuators.
The option can convert the hand-wheel override to a chain driven override in application of actuator mounted at a distance above the floor. It is available for OM-2 to OM-13,OM-F,OM-G actuators.
The option can be connected all wires by the user without removing actuator cover and it is available for OM-2 to OM-13,OM-F,OM-G actuators.
when a set of control wire or switch needs to control two or more actuators at the same time.
Modbus RTU RS485
Available for:
※OM-2 to 6, F, G, H 110-120VAC/1-PH, 30% duty cycle
※OM-2 to 8, F, G, H 220-240VAC/1-PH, 30% duty cycle
※OM-2 to 8, H 110-240VAC/1-PH, 75% duty cycle
※OM-9 to 13, 110-240VAC/1-PH, 50% duty cycle
The combination of quarter-turn electric actuators with a Thermal Insulation Blanket is designed to remove and re-install easily. It makes the actuator run smoothly even in high temperature environment.
Working conditions:
※ Withstand two hours at 250°C (482°F).
※ Withstand one hour at 300°C (572°F).
Available for OM-A, OM-AM, OM-1 to OM-8 floating control.
IP 68(7m, 72 hrs).
Standard: IEC 60529 Edition 2.1: 2001.