Product Name : OM-1
Description
Power:10W
Max Torque:35 N‧m/310 in‧lb
Speed:12 Sec/90°
Weight:2 kg/4.4 lb
Manual Override:Lever
Mounting Flange(ISO 5211):F03/F05

Enclosure :

  • IP67、NEMA 4X : Waterproof and dustproof enclosure.
  • Aluminum alloy, polyester powder coated.

Motor :

  • Insulation class F
  • Optional : Insulation class  H
  • Built-in thermal protection prevents motor burnout.

AC motor:125±5℃/257±9℉
DC motor:90±5℃/194±9℉

Duty Cycle :

  • OM-1:30% duty cycle

Service Condition :

  • Ambient temperature:-30℃ to +65℃ / -22℉ to +149℉
  • The humidity:30% to 95%

Position Indicator :

  • All models have continuous mechanism position indicator on the top of actuator cover.

Gear Train :

  • Gear trains have been already lubricated sufficiently with anti-high temperature lubricant at the factory.

Conduit entries :

  • Standard : 1/2" PS
  • Optional : 1/2"PF, 1/2”NPT or M20

Various voltage :

  • AC/DC 12V
  • AC/DC 24V
  • AC 110/220V,1-Phase

Optional Coating:

  • Nylon coating
  • E.D. coating
  • Epoxy coating

Communication Protocols :

  • Modbus RTU RS485

Working angle :

  • Standard : 0-90°
  • Optional : 91-270°
ModelMax TorqueWeightManual Override
N.min‧lbKglb
OM-A 50 445 3 6.6 N/A
OM-AM 50 445 3 6.6 Lever
OM-1 35 310 2 4.4 Lever
BM-2 120 1065 5.5 13 N/A
OM-F 65 575 11 25 Hand-Wheel
OM-2 90 800 11 25 Hand-Wheel
OM-G 120 1065 11 25 Hand-Wheel
OM-3 150 1330 11 25 Hand-Wheel
OM-H 300 2655 17 38 Hand-Wheel
OM-4 400 3540 20 45 Hand-Wheel
OM-5 500 4430 20 45 Hand-Wheel
OM-6 650 5755 20 45 Hand-Wheel
OM-7 1000 8855 32 71 Hand-Wheel
OM-8 1500 13280 32 71 Hand-Wheel
OM-9 2000 17710 71 157 Hand-Wheel
OM-10 2500 22140 71 157 Hand-Wheel
OM-11 3000 26565 72 159 Hand-Wheel
OM-12 3500 31000 72 159 Hand-Wheel
OM-13 4500 40000 106 234 Hand-Wheel
Model Flange Type Shaft Depth of shaft Key
(ISO 5211) mm inch mm inch mm inch
BM-2 F07 22 0.87 30 1.18 N/A
OM-A F05/F07 17 0.67 20 0.78 N/A
OM-AM F05/F07 17 0.67 20 0.78 N/A
OM-1 F03/F05 14 0.55 17 0.67 N/A
OM-F F07/F10 22 0.87 30 1.18 N/A
OM-G F07/F10 22 0.87 30 1.18 N/A
OM-2 F07/F10 22 0.87 30 1.18 N/A
OM-3 F07/F10 22 0.87 30 1.18 N/A
OM-H F07/F10 22 0.87 30 1.18 N/A
OM-4 F10/F12 36 1.38 40 1.57 N/A
OM-5 F10/F12 36 1.38 40 1.57 N/A
OM-6 F10/F12 36 1.38 40 1.57 N/A
OM-7 F12 or F14 36 1.41 60 2.36 10*10 0.39*0.39
OM-8 F12 or F14 36 1.41 60 2.36 10*10 0.39*0.39
OM-9 F14 or F16 75 2.95 100 3.94 12*10 0.47*0.39
OM-10 F14 or F16 75 2.95 100 3.94 12*10 0.47*0.39
OM-11 F14 or F16 75 2.95 100 3.94 12*10 0.47*0.39
OM-12 F14 or F16 75 2.95 100 3.94 12*10 0.47*0.39
OM-13 F16/F25 72 2.83 110 4.33 20*12 0.79*0.47
  • CE
  • CSA
  • RoHS

proimages/product/OM/OM1.png

Space heater

A space heater can increase the internal temperature and keep dry inside actuator to avoid the freezing lubricant and moisture causing actuator failure under low temperature or high humidity. Heater is not recommended if the ambient temperature is above 35℃/95℉. However, when the temperature varies much from day to night or between summer and winter, heater and thermostat (25±5℃/77±9℉) are recommended.

Heater thermostat

The option can switch the heater off when the temperature inside the actuator is over 25℃/77℉.

Additional limit switches

The standard model equips with the 1st & 2nd switches for fully-open and fully-closed. The option consists of the 3rd & 4th auxiliary switches which provide dry contacts for fully-open and fully-closed.

Current position transmitter

The option can provide 4-20mA output signal for position indicator and etc.

The picture is based on DC 24V

Modulating controller

Actuator can be operated according to input signal and provide the output signal for indicator. Input signal : 4-20mA, 1-5V, 2-10V. Output signal : 4-20mA, 2-10V.

OM-1、OM-A、OM-AM
The pictures are based on AC 110/220V

75% duty cycle (IEC standard)

The option is suggested for higher starting frequency.

OM-1、OM-A、OM-AM:75% duty cycle
The pictures are based on AC 110/220V

Potentiometer unit

The option can be ordered with On/Off actuators.

The selection has 1k or 5k ohm resistance values.

It provides feedback signal for position indicator.

Coupling wiring

when a set of control wire or switch needs to control two or more actuators at the same time.

OM-1, OM-A, OM-AM