OM-J ELECTRIC VALVES ACTUATOR
Enclosure :
- NEMA 4X & IP67 (Waterproof and dustproof enclosure intended for outdoor use).
- Aluminum alloy, polyester powder coated.
- Corrosion protection C3 according to ISO 12944-6.
Motor :
- Insulation class F
- Built-in thermal protection prevents motor burning out.
Duty Cycle :
- 30% duty cycle
- 75% duty cycle is not available
Working Conditions :
- Ambient temperature:-30℃ to +65℃ (-22℉ to +149℉)
- Relative humidity:30% to 95%
Position Indicator :
- Mechanical position indicator on the top of actuator cover.
Gear Train :
- Gear trains have been already lubricated sufficiently with anti-high temperature lubricant at the factory.
Conduit entrance :
- Standard : 1/2" PS
- Optional : 3/4" PF, 1/2" NPT, M20
Voltage :
- AC 24V
- AC 110V
Enclosure :
- Nylon coating
- E.D. coating
- Epoxy coating
Model | Torque | |
---|---|---|
N‧m | in‧lb | |
BM-2 | 120 | 1065 |
OM-A | 50 | 445 |
OM-AM | 50 | 445 |
OM-1 | 35 | 310 |
OM-F | 65 | 575 |
OM-J | 80 | 708 |
OM-2 | 90 | 800 |
OM-G | 120 | 1065 |
OM-3 | 150 | 1330 |
OM-H | 300 | 2655 |
OM-4 | 400 | 3540 |
OM-5 | 500 | 4430 |
OM-6 | 650 | 5755 |
OM-7 | 1000 | 8855 |
OM-8 | 1500 | 13280 |
OM-9 | 2000 | 17710 |
OM-10 | 2500 | 22140 |
OM-11 | 3000 | 26565 |
OM-12 | 3500 | 31000 |
OM-13 | 4500 | 40000 |
Weight | Flange Type | Shaft | Depth of Shaft | Manual Override | |||
---|---|---|---|---|---|---|---|
kg | lb | ISO 5211 | mm | inch | mm | inch | |
5.5 | 12.1 | F07 | 22 | 0.886 | 35 | 1.377 | N/A |
3 | 6.6 | F05/F07 | 17 | 0.669 | 20 | 0.787 | N/A |
3 | 6.6 | F05/F07 | 17 | 0.669 | 20 | 0.787 | Lever |
2 | 4.4 | F03/F05 | 14 | 0.551 | 17 | 0.669 | Lever |
11 | 24.3 | F07/F10 | 22 | 0.886 | 30 | 1.181 | Hand-Wheel |
3 | 6.6 | F05/F07 | 17 | 0.669 | 20 | 0.787 | Lever |
10.5 | 23.1 | F07/F10 | 22 | 0.886 | 30 | 1.181 | Hand-Wheel |
11 | 24.3 | F07/F10 | 22 | 0.886 | 30 | 1.181 | Hand-Wheel |
10.5 | 23.1 | F07/F10 | 22 | 0.886 | 30 | 1.181 | Hand-Wheel |
15 | 33.1 | F07/F10 | 22 | 0.886 | 30 | 1.181 | Hand-Wheel |
20 | 44.1 | F10/F12 | 36 | 1.417 | 40 | 1.574 | Hand-Wheel |
20 | 44.1 | F10/F12 | 36 | 1.417 | 40 | 1.574 | Hand-Wheel |
20 | 44.1 | F10/F12 | 36 | 1.417 | 40 | 1.574 | Hand-Wheel |
36 | 79.4 | F12 or F14 | 35 | 1.377 | 60 | 2.362 | Hand-Wheel |
36 | 79.4 | F12 or F14 | 35 | 1.377 | 60 | 2.362 | Hand-Wheel |
68.5 | 151 | F14 or F16 | 75 | 2.952 | 100 | 3.937 | Hand-Wheel |
68.5 | 151 | F14 or F16 | 75 | 2.952 | 100 | 3.937 | Hand-Wheel |
68.5 | 151 | F14 or F16 | 75 | 2.952 | 100 | 3.937 | Hand-Wheel |
68.5 | 151 | F14 or F16 | 75 | 2.952 | 100 | 3.937 | Hand-Wheel |
102.5 | 226 | F16/F25 | 72 | 2.834 | 110 | 4.33 | Hand-Wheel |
- CE
- CSA
- UKCA
- RoHS
Space heater
A space heater can increase the internal temperature and keep dry inside actuator to avoid the freezing lubricant and moisture causing actuator failure under low temperature or high humidity. Heater is not recommended if the ambient temperature is higher than 35℃ (95℉). However, when the temperature varies much from day to night or between summer and winter, heater and thermostat are recommended.

Heater thermostat
The option can switch the heater off when the temperature inside the actuator is over 25±5℃(77±9℉).

Additional limit switches
The standard model equips with the 1st & 2nd switches for fully-open and fully-closed. The option consists of the 3rd & 4th auxiliary switches which provide dry contacts for fully-open and fully-closed.

Potentiometer unit
The option can be ordered with On/Off actuators.
The selection has 1k or 5k ohm resistance values.
It provides feedback signal for position indicator.