Product Name : S-3600 spring return actuator
Description
Torque:360 Nm / 3185 in-lb
Standard Unit Weight:103 kg / 228 lb
Weight of the Actuator with Manual Override Option:152 kg / 336 lb
Mounting Flange:ISO 5211 F12

Standard Capability :

  • Duty cycle rating:50% (-40℃ to 40℃)、30% (41℃ to 65℃) (Conform to IEC standard).
  • ON/OFF control.

Ambient Temperature Range :

  • Temperature:-30℃ to +65℃/-22℉ to +149℉
  • Humidity:30% to 95%

Enclosure :

  • IP68 (7m, 72 hrs), NEMA 4X / 5
  • Dry powder coated aluminum alloy

Lubrication :

  • Gear trains have been already lubricated sufficiently with anti-high temperature grease at the factory.

Position Indicator :

  • Visual mechanical position indicator.

Voltages :

  • AC/DC 24V (not available with floating or modulating control)
  • AC 110V, 220V - 1 Phase (not available with floating or modulating control)

Conduit entry :

  • Standard:2 x 1/2" NPT
  • Optional:2 x 3/4" NPT, 2 x M20

ModelTorqueMotor PowerWeightMounting Interface
Nmin‧lbStandardW / Manual OverrideFlange TypeOutput DriveDepth of Output Drive
KglbKglbISO 5211mminchmminch
S-500 50 445 50 27 37 60 82 F07 17 0.669 30 1.181
S-1300 130 1150 130 57 77 126 170 F10 22 0.866 41 1.614
S-2000 200 1770 130 93 131.5 205 290 F12 27 1.062 45 1.772
S-2600 260 2300 130 95 133.5 210 295 F12 27 1.062 45 1.772
S-3600 360 3185 130 103 152 228 336 F12 36 1.417 43 1.693
  • CE
  • CSA

proimages/product/S/SH36S01A-en-2023-Jul.jpg

Space heater

A space heater can increase the internal temperature and keep dry inside actuator to avoid the freezing lubricant and moisture causing actuator failure under low temperature or high humidity. Heater is not recommended if the ambient temperature is above 35℃/95℉. However, when the temperature varies much from day to night or between summer and winter, heater and thermostat (25±5℃/77±9℉) are recommended.

proimages/加熱器.png

Heater thermostat

The option can switch the heater off when the temperature inside the actuator is over 25±5°C (77±9°F).

Additional limit switches

The standard model equips with the 1st & 2nd switches for fully-open and fully-closed. The option consists of the 3rd & 4th auxiliary switches which provide dry contacts for fully-open and fully-closed.

proimages/options/pro-39.jpg

Operating direction

Standard : Fail clockwise on loss of power.

Optional : Fail counter-clockwise on loss of power.

proimages/options/s500-3600-1-e.jpg

Manual override

proimages/options/s500-3600-2-e.jpg
您有最新消息