- Home
- Electric Actuators
- Electric Actuators
- Spring Return Fail-Safe Electric Valve Actuators / S Series
- S-3600
S-3600 spring return actuator
Standard Capability :
- Duty cycle rating:50% (-40℃ to 40℃)、30% (41℃ to 65℃) (Conform to IEC standard).
- ON/OFF control.
Ambient Temperature Range :
- Temperature:-30℃ to +65℃/-22℉ to +149℉
- Humidity:30% to 95%
Enclosure :
- IP68 (7m, 72 hrs), NEMA 4X / 5
- Dry powder coated aluminum alloy
Lubrication :
- Gear trains have been already lubricated sufficiently with anti-high temperature grease at the factory.
Position Indicator :
- Visual mechanical position indicator.
Voltages :
- AC/DC 24V (not available with floating or modulating control)
- AC 110V, 220V - 1 Phase (not available with floating or modulating control)
Conduit entry :
- Standard:2 x 1/2" NPT
- Optional:2 x 3/4" NPT, 2 x M20
Model | Torque | Motor Power | Weight | Mounting Interface | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Nm | in‧lb | Standard | W / Manual Override | Flange Type | Output Drive | Depth of Output Drive | ||||||
Kg | lb | Kg | lb | ISO 5211 | mm | inch | mm | inch | ||||
S-500 | 50 | 445 | 50 | 27 | 37 | 60 | 82 | F07 | 17 | 0.669 | 30 | 1.181 |
S-1300 | 130 | 1150 | 130 | 57 | 77 | 126 | 170 | F10 | 22 | 0.866 | 41 | 1.614 |
S-2000 | 200 | 1770 | 130 | 93 | 131.5 | 205 | 290 | F12 | 27 | 1.062 | 45 | 1.772 |
S-2600 | 260 | 2300 | 130 | 95 | 133.5 | 210 | 295 | F12 | 27 | 1.062 | 45 | 1.772 |
S-3600 | 360 | 3185 | 130 | 103 | 152 | 228 | 336 | F12 | 36 | 1.417 | 43 | 1.693 |
- CE
- CSA
Space heater
A space heater can increase the internal temperature and keep dry inside actuator to avoid the freezing lubricant and moisture causing actuator failure under low temperature or high humidity. Heater is not recommended if the ambient temperature is above 35℃/95℉. However, when the temperature varies much from day to night or between summer and winter, heater and thermostat (25±5℃/77±9℉) are recommended.
Heater thermostat
The option can switch the heater off when the temperature inside the actuator is over 25±5°C (77±9°F).
Additional limit switches
The standard model equips with the 1st & 2nd switches for fully-open and fully-closed. The option consists of the 3rd & 4th auxiliary switches which provide dry contacts for fully-open and fully-closed.
Operating direction
Standard : Fail clockwise on loss of power.
Optional : Fail counter-clockwise on loss of power.